The comprehensive flowmeters resource
HomeContact usSite MapLinks+Other info
Relevant sites
Types of Flowmeters
Thermal Mass
Coriolis Mass
Rotameter
Positive Displacement
Vortex shedding
Multiphase
Turbine

Air & Gas Flowmeter
Calorimetric
Compound
Compressed air
Electromagnetic
Flumes & Weirs
Laminar Mass
Large Pipe
Low Flow
Medical
Open Channel
Orifice plate
Paddle Meter
Ultrasonic
Variable Area
Venturi
Doppler
OEM Flow meter
>>Flowmeters
Related Products
Flowmeter Rental
Refurbished Flow meter
Watercut meters
Flow Sensors
Flow nozzles
Flow Straighteners / Conditioners
Custody Transfer Oil and Gas Sampling Systems

Hydraulic Flowmeters
Batching / Bulk meters
Sight Glass /Sight Flow Indicator
Air Eliminators
Automatic Meter Reading
Flowmeter Indicators Panels
Flow Computers
Flow Switches
Flow Software
Water Meters
High Temperature Flow meters
  Submitted Articles: ARTC06080101
Article: Venturi Flow Meter Misconceptions, Truths, and Poor Standard Practices
Submitted by: John Davis
Submit date: 01/08/06

Introduction

There seems to be a trend of different types of flow meters not performing correctly in Water and Wastewater plants. This paper will try to explain some of the causes and ways of correcting certain problems. In my previous ISA article titled Understanding Flow Metering Specifications, the installation, turndown, repeatability, and velocity were all important components for a magnetic flow meter’s performance and accuracy. For this particular article I will address some misconceptions, truths, and poor standard practices associated with venturi flow meters.

Piping Configuration

A common problem which can cause errors in accuracy is improper piping installations. Many consultants will design a treatment plant or a reclaim water application utilizing a venturi tube. In most cases, due to the constraints of the area in which a water treatment or a water reclamation plants are generally designed, piping laying length considerations normally seem less than ideal. This is especially true with regards to older plants when expanding the plant with new process tanks, mechanical equipment, and piping is required. The consultant will generally try to locate the flow meter where it is best possibly suited. The consultants are generally at an understanding that the venturi flow meters are very accurate. One of the misconceptions is the consultants and end users also believe that the flow certification document from the flow laboratory is directly related to their flow meter installed design. Warning, the flow certificate document can unintentionally be misleading.
A venturi tube is sensitive to flow profiles due to the actual design of the tube. In many cases venturi tubes are always surrounded with piping elbows, tees, piping increasers, piping reducers, and valves. All of these have significant impacts depending on what distance they are located upstream and downstream of the flow meter in regards to accuracy.

Accuracy Statement

A venturi manufacturer accuracy statement is usually generated from a tested result provided from a flow laboratory. The misconception is that the end user doesn’t realize that the flow laboratory will usually install the flow tube in a smooth pipe at an ideal condition where upstream and downstream flow constraints will not impede a proper flow profile. The truth is that the flow meter that was installed and tested at the flow laboratory may not mimic the actual installed condition required at the plant.

Another truth is the flow laboratory’s test procedure is not documented well enough for the consultant or end user to verify if the flow meter had matched the required installed condition for the plant. This, in my opinion, leaves in doubt the test result and the certification of that flow tube’s flow coefficient from the manufacturer. This problem can easily be avoided if the consultant when designing the system gives the manufacturer actual laying lengths of upstream and downstream conditions, pipe size, pipe material, minimum and maximum design flow rates, and the type of solution flowing in the pipe.

Another recommendation to consultants and end users, while the plant is in the design phase, ask the manufacturer to review the contract specifications for the flow meter.

The venturi tube material and installation may not necessarily be correct for that design application. Remember that the accuracy statement along with the coefficient number will change on that tube depending on its location and how the flow profile looks.

Let’s look at a misconception in how using the Reynolds’s Number alone, without adding to the equation the relative roughness of the pipe, can give you an ideal Reynolds Number.

You have been asked to provide by a project manager an 18”influent venturi flow meter for a wastewater treatment plant. The minimum flow rate that needs to be monitored is 500gpm and the maximum is 5000gpm. In addition, the flow meter is installed on ductile pipe.

After crunching out the Reynolds number for minimum and maximum flows you find at minimum flow your number yields approximately 88,000 and your maximum flow produces a number of 887,000. The problem is that although at minimum flow the Reynolds number indicates greater than 75,000, you also find that the velocity is only a little greater than .6ft/sec. The use of the Reynolds Number alone did not give a proper evaluation for the ability of reading and measuring with accuracy the minimum flow. As earlier stated the flow laboratory may be using smooth pipe in its testing procedure and in your design, you may be using ductile pipe. The truth is that piping material matters greatly when determining turbulent conditions in pipes. This is very well depicted in hydraulic books that show the Moody diagram which actually shows the relationship of relative roughness to flow conditions. My recommendation is to use the relative roughness equation in your calculations when using the Reynolds Number. In my experience this gets over looked as being insignificant and so consultants and end users must be careful. These types of meters are used for various flow control applications like chemical dosing, where accuracy does become critical.

Turndown Capability

This also brings up a misconception issue with regards to the differential pressure transmitter with stated 200:1 turn downs. The truth is that you can not assume that you can measure differential at 1/200th “H2O. The transmitter may be accurate on a test stand but the physical hydraulic constraints of the installed venturi flow meter with respect to velocity may not always let you measure that low of a differential pressure with high accuracy. Typically a venturi tube will have at best an 8:1 turndown. The manufacturer who publishes a 200:1 turndown on differential pressure transmitters are not distinguishing that the transmitter is on a venturi tube and neither should the consultant or end user. The manufacturer’s accuracy statement on these type of transmitters is also not based on actual field conditions of any given venturi tube. The 200:1 turndown does not have any real relationship with the 8: 1 turn down capability of the venturi flow meter. In addition, if any manufacturer suggests that two transmitters on a venturi tube will give the end user a higher accuracy performance, the consultant or end user may what to review actual installation and flow requirements.

Field Calibration and Inspection Ports

In some cases there are calibration procedures for venturi tubes being misapplied. The misconception that the end user will get a high accuracy performance from a digital manometer as a calibration device for venturi tubes is erroneous. The digital manometer is not a proper calibration device because it only looks at the differential pressure transmitter diaphragms and not the flow tube. A plant operator calibrating the flow meter generally needs to zero out the differential pressure transmitter to produce (4madc). This is generally done by allowing the 3 or 5-way manifold to be equalized at both the high and low side. If zero is not present than that person will adjust the span until they get a zero reading. Now what that person just did is to unknowingly eliminate the error which could be caused by the displacement of the diaphragms. The person has no idea at that point if the diaphragm is at a factory standard tolerance or if any of the diaphragms should be replaced. What also is a problem, there isn’t any way of knowing the true accuracy of the flow system.

In my own documented experiences seeing actual field conditions of venturi tubes, when a plant is using a digital manometer, there are generally other errors associated with that flow meter’s installation. For instance, the proper manometer to check the tube itself is not purchased or used; there is no flushing or rodding out connections for the high and low static pipes, no manometer or flushing taps present. The static tubing from the flow tube to the differential pressure transmitter may not to be rigid tubing but flexible polyethylene tubing. This flexible tubing can allow vibration to occur allowing additional errors to be created. At this time I do not know of any published documentation from any manufacturer of transmitters showing an end user how to detect that the degree of displacement in the diaphragm at rest is out of factory tolerances for its stated accuracy. This problem needs to be addressed by the manufacturers either in their operation manuals or at their training seminars.

I’m seeing more of these digital manometers being used for calibration purposes in various plants as an acceptable standard practice. In my opinion the use of a digital manometer is a poor standard practice as a recommended calibration tool for a venturi flow meter. The flow meter manufacturers should play a more pro-active role in resolving this problem. The manufacturers should remember that end users are relying on their expertise to help in assuring that proper procedures associated with their equipment are in compliance with the end user’s needs.

The flow tube, if correctly tested for actual installed condition, should have a proper flow coefficient and a calibrated differential vs. flow curve assigned to that tube. The truth is without checking the actual differential pressure using a manometer (mercury or oil filled) against the documented flow curve; a plant operator would have no idea if there is an actual problem with the flow tube itself. Problems such as the static pipes (high and low) could be clogged, coating on the inside lining of the tube could be present. Coating could be from buildup due to tuberculation or sludge build up. Most pipe buildups occur due to solids falling out of suspension from low velocity flow conditions.

I would like to recommend more than one inspection port for a venturi flow tube, one inspection port at the inlet and the other inspection port at the outlet of the flow meter. Typically the highest scouring velocity is located at the throat of the venturi tube (where the low tap side is located) which would generally mean that tuberculation or sludge buildup at the throat would not be present. However this would not be true for the inlet section where the high tap is located. If an inspection port was located upstream and downstream near the flow meter, an operator could inspect and clean more frequently the inside of the flow tube and just as critical, the pipe.

Combined Electrical and Process Equipment Panel with Pressurized Water Piping

In regards to good standard practices, I have been alarmed at seeing dangerous installation procedures. The one that stands out mostly is the installation of high service pumps with the use of a effluent distribution pressure transmitter and a high and low pressure switch mounted in a stainless steel panel with pressurized tubing, a power supply to the pressure transmitter, and remote power sources wired to terminal blocks for the pressure switches.

There is a probable chance that the pressurized tubing could leak in the panel. Water spraying inside any panel which has circuit breakers, power supplies, or remote power sources wired to terminal blocks is extremely dangerous.

My recommendation is for end users to investigate their plants to see if these types of panels exist and to immediately take a proactive role to correct these installations. The end users should move all transmitters and pressure switches that are attached to pressurized tubing out of panels which have power and wired terminal blocks. The Transmitter, pressure switches, and pressure lines can be mounted on a field rack. If the field rack is required to be located outdoors, provide sunshields. A separate electrical panel should be provided that allows water tight conduit and wire to the process equipment. Now if the pressurized tubing leaks it should not have any hazardous effect.

Summary

I would like to recap the following critical points:

  1. Installed piping constraints play a large role in the accuracy of the flow meter.
  2. The Reynolds’s Number alone can not be the final determiner for evaluating the accuracies of minimum and maximum flow requirements.
  3. Use the relative roughness equation with your Reynolds Number evaluation.
  4. Understand the actual relationship of a turndown ratio.
  5. Good calibration techniques with periodic maintenance equates to a high accuracy condition.
  6. Do not mix water and electricity together.

In my many years of dealing with venturi manufacturers I found them very helpful during the early design phases of my projects. They will generally review drawings and contract specifications. As stated before if you give them the minimum and maximum flow requirements, a drawing showing the installed flow meter with the upstream and downstream conditions, piping material, pipe size, and type of solution flowing in the pipe they will give you a flow meter that will actually fit your installed requirements. Generally if you give the manufacturer too many unknowns, they will return the favor and let you know that the actual accuracy will be unknown. It is generally not a good idea to wait for startup construction service to begin before you find out that the flow meter may not be suited for the application.

John Davis is an Senior Member of ISA who Operates Davis Instrumentation Services.
His e-mail address is Nira47@aol.com

 


This article was submitted by John Davis