Another advantage
is its flexibility in handling a wide range
of chemicals. Today, all-Teflon meters are available
to resist corrosive damage by aggressive chemicals.
The advantage of a Teflon flowmeter with a built-in
valve is that you can not only monitor the fluid
flowrate, but you can control it, as well, by
opening and closing the valve. If the application
requires an all-Teflon meter, chances are the
fluid is pretty corrosive, and many users would
like the option of controlling the flowrate
by simply turning a valve that is built into
the flowmeter itself.
Disadvantages: One potential disadvantage of
a variable-area flowmeter occurs when the fluid
temperature and pressure deviate from the calibration
temperature and pressure. Because temperature
and pressure variations will cause a gas to
expand and contract, thereby changing density
and viscosity, the calibration of a particular
variable-area flowmeter will no longer be valid
as these conditions fluctuate. Manufacturers
typically calibrate their gas flowmeters to
a standard temperature and pressure (usually
70°F with the flowmeter outlet open to the
atmosphere, i.e., with no backpressure).
During operation, the flowmeter accuracy can
quickly degrade once the temperatures and pressures
start fluctuating from the standard calibration
temperature and pressure. Meters used for water
tend to show less variability, since water viscosity
and density changes very little with normal
temperature and pressure fluctuations. While
there is a way to correlate the flow from actual
operating conditions back to the calibration
conditions, the conventional formulas used are
very simplified, and don't take into account
the effect of viscosity, which can cause large
errors
Table 2
The Effect of Pressure Deviations on a Variable-Area
Flowmeter

As Table 2 shows, the effect of pressure deviations
can be quite significant. This table was created
using data from a variable-area flowmeter that
was calibrated for air at 70°F and with
the outlet of the flowmeter vented to the open
atmosphere (i.e. , 0 psi of outlet pressure).
The flowmeter was calibrated to read a maximum
of 2.23 L/min at this temperature and pressure.
When the outlet pressure increases as all other
parameters remain constant, the flowrate drops
off. This pressure change affects the viscosity
and density of the gas and will cause the actual
flowrate to deviate from the theoretical, calibrated
flowrate. This relationship is extremely important
to be aware of, and underscores the difficulty
in measuring gas flow. Also note that even though
gas flowrate changes with a change in gas temperature
(with all other parameters remaining constant),
this effect is much less significant with air
than with other gases.
Table 2 shows this same variation with a meter
calibrated for water at 9 psi venting pressure
and a temperature of 70°F. Here, one can
assume water to be incompressible. As shown,
there is no direct effect on water flow with
a change in back-pressure. The temp-erature
change is not that significant either. But,
for various fluids, a change in temperature
could change the viscosity enough to degrade
the accuracy below acceptable limits.
The bottom line is that the user must be aware
of any variation between calibration conditions
and operating conditions for gas flows, and
must correct the reading according to the manufacturer's
recommendations. Some users have the manufacturer
calibrate the meter to existing conditions,
but this presumes that operating conditions
will remain the same—which they rarely
do.
The effect of viscosity changes is another
potential disadvantage of the variable-area
meter when measuring liquids. When a viscous
liquid makes its way through a variable-area
flowmeter, drag layers of fluid will build up
on the float. this will cause a slower-moving
viscous liquid to yield the same buoyant force
as a faster-moving fluid of lower viscosity.
The larger the viscosity, the higher the error.
The general rule of thumb is as follows—unless
the meter has been specifically calibrated for
a higher-viscosity liquid, only water-like liquids
should be run through a variable-area flowmeter.
Sometimes, for liquids that are slightly thicker
than water, a manufacturer-supplied correction
factor can be used without the need to recalibrate
the whole meter. As always, check with the manufacturer
if you plan on deviating from its calibration
fluid and calibration conditions. For a more-detailed
discussion of the proper correction equations
to apply to variable-area flowmeters in both
water and gas service when they deviate from
standard conditions, consult Refs. 9 and 10.
Applications:
Variable-area flowmeters are well suited for
a wide variety of liquid and gas applications,
including the following:
- Measuring water and gas flow in plants or
labs
- Monitoring chemical lines
- Purging instrument air lines (i.e., lines
that use a valved meter)
- Monitoring filtration loading
- Monitoring flow in material-blending applications
(i.e., lines that use a valved meter)
- Monitoring hydraulic oils (although this
may require special calibration)
- Monitor makeup water for food & beverage
plants
|